NZBC B1.3.2 requires building elements (including storage water heaters) to be adequately supported including support against earthquake forces. The method illustrated in Figure 14 is acceptable for water heaters up to 360 litre capacity. Where fittings and pipework are attached to the water heater through the supporting platform or floor a 50 mm minimum clearance shall be provided between the fitting and the support structure. 6.11.5 An alternative acceptable solution for securing storage water heaters against seismic forces is given in Section 203 of NZS 4603.
Seismic Restraint for Hot Water Cylinder
NZBC B1.3.2 requires building elements (including storage water heaters) to be adequately supported including support against earthquake forces.
Description
NZBC B1.3.2 requires building elements (including storage water heaters) to be adequately supported including support against earthquake forces. The method illustrated in Figure 14 is acceptable for water heaters up to 360 litre capacity. Where fittings and pipework are attached to the water heater through the supporting platform or floor a 50 mm minimum clearance shall be provided between the fitting and the support structure. 6.11.5 An alternative acceptable solution for securing storage water heaters against seismic forces is given in Section 203 of NZS 4603.
Related products
80/125mm 45 Degree Elbow Pack of 2
Add to Quote60/100mm Extension Flue Kit Short 220mm
Add to Quote80/125mm Horizontal Flue Kit 1200mm
Add to Quote